Is the Cummins RS25 the Right 25kW Standby Generator for Your Facility?
The Cummins RS25 Quiet Connect (part number A051Y399) is a 25kW liquid-cooled standby generator built for 120/208V three-phase service. It delivers 86.7 amps at full load, starts and transfers automatically under its PowerCommand 1.1 control, and is capable of meeting NFPA 110 requirements when equipped with the necessary accessories and properly installed. It runs on natural gas or propane vapor, selectable in the field.
It's sized for businesses that have outgrown a residential home standby but don't need a 100kW-class genset: professional and medical offices, retail, restaurants, churches and small light-commercial buildings on 208V three-phase service. The compact Quiet Connect enclosure measures 72 x 34 x 45.5 inches and weighs 1,109 lb, so it fits sites where larger commercial units won't.
Mighty Generators supplies the RS25 by quote. Cummins builds it to order and ships it freight direct, typically in 5 to 6 weeks, so you can have the pad, fuel line and transfer switch ready while it's in production.
Cummins RS25 at a Glance
- Standby rating: 25 kW, 60 Hz
- Electrical: 120/208V three-phase, 86.7 A rated, a 100 A circuit breaker
- Engine: Cummins 2.4L naturally aspirated in-line 4-cylinder, 1800 rpm
- Fuel: Natural gas or propane vapor, selectable in the field (single fuel, not both at once)
- Controller: Cummins PowerCommand 1.1
- Sound: 64 dB(A) at 23 ft (7 m) with the optional Sound Level 2 enclosure
- Size and weight: 72 x 34 x 45.5 in (L x W x H), 1,109 lb
- Code compliance: UL 2200, EPA stationary emergency (40 CFR 60), IBC seismic, NFPA 110 capable
Cummins RS25 Features and Performance
Engine and Fuel
The Cummins 2.4L naturally aspirated in-line 4-cylinder runs at 1800 rpm with an isochronous electronic governor, so frequency holds steady as loads switch on and off. It's a single-fuel engine that can be set up for natural gas or propane vapor in the field. At full load it uses 309.5 cubic feet per hour of natural gas or 3.5 gallons per hour of propane.
PowerCommand 1.1 Control
PowerCommand handles automatic remote starting and stopping, voltage and frequency regulation, alarm and status display, output metering and automatic shutdown when it detects a fault. Voltage regulation is ±1.0% from no load to full load, and random frequency variation is ±0.25% at 60 Hz (ISO 8528-1 Class G3), which matters when the loads include IT equipment, variable-speed drives or medical devices. The flexible exercise mode lets you choose when and how long the generator runs its test cycle, down to as little as 2 minutes every 6 months, which cuts fuel use and noise on site.
Enclosure and Weather
The powder-coated aluminum enclosure comes in Sound Level 1 trim with the muffler installed, in sandstone. Cummins has evaluated it to withstand 180 mph wind loads under ASCE 7-10, and hinged doors open for service. Cummins publishes its sound rating with the optional Sound Level 2 upgrade kit fitted: 64 dB(A) at 23 ft (7 m). If a property line or local noise ordinance is tight, quote the upgrade kit with the generator. Cummins designs the RS25 to start in temperatures as low as -40°F, and the factory coolant heater keeps the engine ready to take load.
Where the Cummins RS25 Fits
Start with the electrical service. This RS25 is wired for 120/208V three-phase. Cummins builds the RS25 for 120/240V single-phase and 120/240V three-phase service too, each under its own part number, so if your building has one of those services, ask us to quote the matching model instead of this one.
Typical applications for a three-phase unit this size:
- Medical, dental and veterinary offices that need lights, HVAC, IT and patient equipment through an outage
- Retail stores and restaurants protecting refrigeration, point-of-sale and lighting
- Churches, community buildings and small offices on 208V three-phase service
- Telecom and small server rooms that need regulated, automatic backup
Size the generator from the load, not the square footage. A licensed electrician or engineer should run a load calculation that accounts for motor starting, HVAC and anything on variable-speed drives, and our team can match that number to the right RS model.
Cummins RS25 vs Nearby Quiet Connect Sizes
If your calculated load lands close to 25kW, it's worth looking one size either side before you commit. Here's how the RS25 compares with RS30 in the same 120/208V three-phase configuration.
| Model |
Standby rating |
Rated amps (120/208V) |
Engine |
Weight |
| RS25 |
25 kW |
86.7 A |
2.4L |
1,109 lb |
| RS30 |
30 kW |
104.1 A |
2.4L |
1,231 lb |
The RS25 to RS40 share a compact enclosure and a 2.4L four-cylinder engine. The RS50 to RS100 move to a 5.9L six-cylinder in a 118.7 inch enclosure, and the RS125 and RS150 use an 8.9L engine in a 143 inch green enclosure with PowerCommand 2.3 control.
Planning the Cummins RS25 Installation
-
Transfer switch: sold separately and required. Cummins offers automatic transfer switches in a range of amperages, including service entrance models, all listed to UL 1008.
-
Delivery and pad: the unit weighs 1,109 lb and ships on a pallet, so plan unloading equipment and a pad sized for its 72 x 34 x 45.5 inch footprint.
-
Elevation and heat: Natural gas: full rated output at sea level up to 77°F (25°C); derate 4% per 1,000 ft and 2% per 10°C above 25°C.
-
Accessories worth quoting: Sound Level 1 to Sound Level 2 enclosure upgrade kit, PowerCommand 500 internet monitoring device, HMI211RS in-home remote display, alternator heater, maintenance and service kit.
Cummins RS25 Specifications
| Specification |
Cummins RS25 (A051Y399) |
| Manufacturer |
Cummins |
| Series |
Quiet Connect |
| Model |
RS25 (C25N6) |
| Part number (SKU) |
A051Y399 |
| Standby rating |
25 kW |
| Voltage |
120/208V |
| Phase |
Three-phase |
| Frequency |
60 Hz |
| Rated amps |
86.7 A |
| Circuit breaker |
100 A |
| Engine |
Cummins 2.4L naturally aspirated in-line 4-cylinder |
| Rated speed |
1800 rpm |
| Fuel |
Natural gas or propane vapor, selectable in the field (single fuel, not both at once) |
| Fuel consumption |
309.5 ft³/hr natural gas or 3.5 gal/hr propane at full load |
| Controller |
PowerCommand 1.1 |
| Voltage regulation |
±1.0%, no load to full load |
| Frequency variation |
±0.25% at 60 Hz (ISO 8528-1 Class G3) |
| Sound |
64 dB(A) at 23 ft (7 m) with the optional Sound Level 2 enclosure |
| Enclosure |
Powder-coated aluminum, Sound Level 1 with muffler installed, sandstone |
| Wind rating |
180 mph (ASCE 7-10) |
| Cold start |
As low as -40°F |
| Dimensions (L x W x H) |
72 x 34 x 45.5 in |
| Weight |
1,109 lb |
| Altitude and temperature |
Natural gas: full rated output at sea level up to 77°F (25°C); derate 4% per 1,000 ft and 2% per 10°C above 25°C |
| Code compliance |
UL 2200; EPA emissions, stationary emergency, 40 CFR 60; IBC seismic; NFPA 110 capable |
| Base warranty |
2 years, standby use (Cummins) |
Standard Equipment on the Cummins Spec Sheet
- Coolant heater
- Crankcase vent heater
- Battery rack
- Flexible fuel line
- Operator's manual and installation manual
Confirm the final configuration and any accessories on your written quote.
Frequently Asked Questions About the Cummins RS25
What electrical service does the Cummins RS25 need?
This RS25 (part number A051Y399) is built for 120/208V three-phase service and is rated 86.7 amps at full load, with a 100 A circuit breaker. Cummins also builds the RS25 for 120/240V single-phase and 120/240V three-phase service under different part numbers, so match the generator to your building's service before you order.
Can the Cummins RS25 run on propane as well as natural gas?
Yes. The RS25 is a single-fuel generator that can be set up for natural gas or propane vapor in the field, though it runs on one fuel at a time, not both. At full load Cummins rates it at 309.5 cubic feet per hour of natural gas or 3.5 gallons per hour of propane, which is what your gas utility or propane supplier will need to size the supply.
Is the Cummins RS25 suitable for an NFPA 110 emergency power system?
Cummins states the RS25 is capable of meeting NFPA 110 requirements when it's equipped with the necessary accessories and properly installed. It's certified to UL 2200 and EPA stationary emergency emissions rules (40 CFR 60) and meets IBC seismic requirements, and its PowerCommand control supports automatic remote start and shutdown on a detected fault. Your engineer of record or the authority having jurisdiction decides what level your facility needs.
How loud is the Cummins RS25?
With the optional Sound Level 2 upgrade kit, Cummins rates the RS25 at 64 dB(A) at 23 ft (7 m). The generator ships in a Sound Level 1 aluminum enclosure with the muffler installed, and the Sound Level 2 kit can be added where a property line or noise ordinance calls for it.
Should I choose the Cummins RS25 or the RS30?
Choose on calculated load and growth. The RS25 is rated 25kW and 86.7 amps at 120/208V three-phase; the RS30 is rated 30kW and 104.1 amps and weighs 1,231 lb against 1,109 lb. If your load calculation lands close to 25kW or you expect to add equipment, the RS30 gives you headroom. Send us your load list with a quote request and we'll recommend the size.
Warranty and Support
Cummins backs the RS25 with a 2-year base warranty when it's used in an EPA stationary emergency (standby) application, and extended Cummins warranties are available. Warranty coverage and service come from Cummins and its certified distributor and dealer network. Mighty Generators is an authorized Cummins dealer: we'll check the configuration against your electrical service, quote the transfer switch and accessories, and coordinate freight to your site.